Piping


Refrigerant Piping
One of the Fundamental Series
A publication of Trane, a business
of American Standard Companies
Preface
© 2002 American Standard Inc. All rights reserved
ii TRG-TRC006-EN
Trane believes that it is incumbent on manufacturers to serve the industry by
regularly disseminating information gathered through laboratory research,
testing programs, and field experience.
The Trane Air Conditioning Clinic series is one means of knowledge sharing. It
is intended to acquaint a technical audience with various fundamental aspects
of heating, ventilating, and air conditioning (HVAC). We have taken special care
to make the clinic as uncommercial and straightforward as possible.
Illustrations of Trane products only appear in cases where they help convey the
message contained in the accompanying text.
This particular clinic introduces the reader to refrigerant piping.
Refrigerant Piping

notes
period one
Refrigerant Piping Requirements
The focus of this clinic is on the design and installation of the interconnecting
piping for vapor-compression refrigeration systems. Reviewing the physical
changes that the refrigerant undergoes within the refrigeration cycle will help
demonstrate certain demands that the piping design must meet.
This clinic focuses on systems that use Refrigerant-22 (R-22). While the general
requirements are the same for systems that use other refrigerants, velocities
and pressure drops will differ.
Figure 3 illustrates a basic vapor-compression refrigeration cycle. Refrigerant
enters the evaporator in the form of a cool, low-pressure mixture of liquid and
vapor (A). Heat is transferred to the refrigerant from the relatively warm air that
is being cooled, causing the liquid refrigerant to boil. The resulting refrigerant
vapor (B) is then pumped from the evaporator by the compressor, which
increases the pressure and temperature of the vapor.
period one
Refrigerant Piping Requirements
Refrigerant Piping Requirements
The resulting hot, high-pressure refrigerant vapor (C) enters the condenser
where heat is transferred to ambient air, which is at a lower temperature than
the refrigerant. Inside the condenser, the refrigerant vapor condenses into a
liquid and is subcooled. This liquid refrigerant (D) then flows from the
condenser to the expansion device. This device creates a pressure drop that
reduces the pressure of the refrigerant to that of the evaporator. At this low
pressure, a small portion of the refrigerant boils (or flashes), cooling the
remaining liquid refrigerant to the desired evaporator temperature. The cool
mixture of liquid and vapor refrigerant (A) enters the evaporator to repeat the
cycle.
The vapor-compression refrigeration cycle, and the four major components of
the refrigeration system (evaporator, compressor, condenser, and expansion
device), are discussed in more detail in separate clinics. Refer to the list of
references at the end of Period Six.
These individual components are connected by refrigerant piping. The suction
line connects the evaporator to the compressor, the discharge line connects the
compressor to the condenser, and the liquid line connects the condenser to the
expansion device. The expansion device is typically located at the end of the
liquid line, at the inlet to the evaporator.
There is more to the design of refrigerant piping than moving refrigerant from
one component to another. Regardless of the care exercised in selection and
application of the components of the refrigeration system, operational
problems may be encountered if the interconnecting piping is improperly
designed or installed.
Interconnecting Refrigerant Piping
compressor
condenser
evaporator
expansion
device
discharge
line
suction
line
liquid
line
Refrigerant Piping Requirements
notes
When a refrigeration system includes field-assembled refrigerant piping to
connect two or more of the components, the primary design goals are generally
to maximize system reliability and minimize installed cost. To accomplish these
two goals, the design of the interconnecting refrigerant piping must meet the
following requirements:
 Return oil to the compressor at the proper rate, at all operating conditions
 Ensure that only liquid refrigerant (no vapor) enters the expansion device
 Minimize system capacity loss that is caused by pressure drop through the
piping and accessories
 Minimize the total refrigerant charge in the system to improve reliability and
minimize installed cost
The first requirement is to ensure that oil is returned to the compressor at all
Refrigerant Piping Requirements
▲ Return oil to compressor
▲ Ensure that only liquid refrigerant enters
the expansion device
▲ Minimize system capacity loss
▲ Minimize refrigerant charge
Figure 5
Scroll Compressor
stationary
scroll
driven
scroll
intake
discharge
intake
discharge
port
motor
shaft
seal
Figure 6
4 TRG-TRC006-EN
notes
period one
Refrigerant Piping Requirements
operating conditions. Oil is used to lubricate and seal the moving parts of a
compressor. For example, the scroll compressor shown in Figure 6 on page 3
uses two scroll configurations, mated face-to-face, to compress the refrigerant
vapor. The tips of these scrolls are fitted with seals that, along with a thin layer
of oil, prevent the compressed refrigerant vapor from escaping through the
mating surfaces. Similarly, other types of compressors also rely on oil for
lubrication and for providing a seal when compressing the refrigerant vapor.
Characteristically, some of this lubricating oil is pumped along with the
refrigerant throughout the rest of the system. While this oil has no function
anywhere else in the system, the refrigerant piping must be designed and
installed so that this oil returns to the compressor at the proper rate, at all
operating conditions.
Returning to the system schematic, droplets of oil are pumped out of the
compressor along with the hot, high-pressure refrigerant vapor. The velocity of
the refrigerant inside the discharge line must be high enough to carry the small
oil droplets through the pipe to the condenser.
Inside the condenser, the refrigerant vapor condenses into a liquid. Liquid
refrigerant and oil have an affinity for each other, so the oil easily moves along
with the liquid refrigerant. From the condenser, this mixture of liquid refrigerant
and oil flows through the liquid line to the expansion device.
Next, the refrigerant–oil mixture is metered through the expansion device into
the evaporator, where the liquid refrigerant absorbs heat and vaporizes. Again,
the velocity of the refrigerant vapor inside the suction line must be high enough
to carry the droplets of oil through the pipe back to the compressor.
Without adequate velocity and proper pipe installation, oil may be trapped out
in the system. If this condition is severe enough, the reduced oil level in the
compressor could cause lubrication problems and, potentially, mechanical
failure.
Return Oil to Compressors
compressor
condenser
evaporator
expansion
device
discharge
line
suction
line
liquid
line
warm
liquid
hot
vapor
cool
vapor
Figure 7
TRG-TRC006-EN 5
period one
Refrigerant Piping Requirements
notes
The second requirement of the refrigerant piping design is to ensure that only
liquid refrigerant enters the expansion device. There are several types of
expansion devices, including expansion valves (thermostatic or electronic),
capillary tubes, and orifices.
In addition to maintaining the pressure difference between the high-pressure
(condenser) and low-pressure (evaporator) sides of the system, a
thermostatic expansion valve (TXV) also controls the quantity of liquid
refrigerant that enters the evaporator. This ensures that the refrigerant will be
completely vaporized within the evaporator, and maintains the proper amount
of superheat in the system.
Inside the condenser, after all of the refrigerant vapor has condensed into
liquid, the refrigerant is subcooled to further lower its temperature. This
subcooled liquid refrigerant leaves the condenser (A) and experiences a
pressure drop as it flows through the liquid line and accessories, such as a filter
Thermostatic Expansion Valve (TXV)
external equalizer
remote
bulb
evaporator
TXV
refrigerant
vapor
distributor
liquid
refrigerant
Figure 8
Subcooling
A B
pressure
enthalpy
subcooling
mixture of liquid
and vapor
saturated
vapor curve
saturated
liquid curve
expansion
device
condenser
evaporator
compressor
Figure 9
6 TRG-TRC006-EN
notes
period one
Refrigerant Piping Requirements
drier and solenoid valve, installed upstream of the TXV. On the pressureenthalpy chart, Figure 9 on page 5, this moves the condition of the refrigerant
toward the saturated liquid curve (B). If this pressure drop is high enough, or if
the refrigerant has not been subcooled enough by the condenser, a small
portion of the refrigerant may boil (or flash), resulting in a mixture of liquid and
vapor (C) entering the expansion device.
The presence of refrigerant vapor upstream of the expansion device is very
undesirable. Bubbles of vapor displace liquid in the port of the TXV, reducing
the flow rate of liquid through the valve, therefore substantially reducing the
capacity of the evaporator. This results in erratic valve operation.
The design of the piping system must ensure that only liquid refrigerant (no
vapor) enters the expansion device. This requires that the condenser provide
adequate subcooling at all system operating conditions, and that the pressure
drop through the liquid line and accessories not be high enough to cause
flashing. Subcooling allows the liquid refrigerant to experience some pressure
drop as it flows through the liquid line, without the risk of flashing.
The third requirement of the refrigerant piping design is to minimize system
capacity loss. To achieve the maximum capacity from the system, the
refrigerant must circulate through the system as efficiently as possible. This
involves minimizing any pressure drop through the piping and other system
components.
Whenever a fluid flows inside a pipe, a characteristic pressure drop is
experienced. Pressure drop is caused by friction between the moving liquid (or
vapor) and the inner walls of the pipe. The total pressure drop depends on the
pipe diameter and length, the number and type of fittings and accessories
installed in the line, and the mass flow rate, density, and viscosity of the
refrigerant.
As an example, the chart in Figure 10 demonstrates the impact of pressure
drop, through the suction line, on the capacity and efficiency of the system. For
this example system operating with Refrigerant-22, increasing the total
Pressure Drop in a Suction Line
period one
Refrigerant Piping Requirements
notes 
pressure drop in the suction line from 3 psi (20.7 kPa) to 6 psi (41.4 kPa)
decreases system capacity by about 2.5 percent and decreases system
efficiency by about 2 percent.
This reveals a compromise that the system designer must deal with. The
diameter of the suction line must be small enough that the resulting refrigerant
velocity is sufficiently high to carry oil droplets through the pipe. However, the
pipe diameter must not be so small that it creates an excessive pressure drop,
reducing system capacity too much.
The first three requirements have remained unchanged for many years.
However, years of observation and troubleshooting has revealed that the lower
the system refrigerant charge, the more reliably the system performs.
Therefore, a fourth requirement has been added for the design of refrigerant
piping: minimize the total amount of refrigerant in the system. To begin with,
this involves laying out the shortest, simplest, and most-direct pipe routing. It
also involves using the smallest pipe diameter possible, particularly for the
liquid line because, of the three lines, it impacts refrigerant charge the most.
The chart in Figure 11 shows that the liquid line is second only to the condenser
in the amount of refrigerant it contains.
This reveals another compromise for the system designer. The diameter of the
liquid line must be as small as possible to minimize the total refrigerant charge.
However, the pipe diameter cannot be small enough to create an excessive
pressure drop that results in flashing before the liquid refrigerant reaches the
expansion device.
Minimize Refrigerant Charge
liquid line suction line
condenser
evaporator
filter
drier
compressor
discharge
line
period one
Refrigerant Piping Requirements
This clinic discusses the processes for sizing the interconnecting piping in an
air-conditioning system. Some of the information required for selecting the
optimal line sizes is best known by the manufacturer. Therefore, if the
manufacturer of the refrigeration equipment provides recommended line sizes,
or tools for selecting the optimal line sizes, we recommend that you use those
line sizes.
If, however, line sizes are not provided by the manufacturer, the processes
outlined within this clinic could be used for selecting the sizes.
Before discussing the design and installation of the suction, discharge, and
liquid lines, there are some general requirements that apply to all of these lines.
First, copper tubing is typically used for refrigerant piping in air-conditioning
systems. This tubing is available in various standard diameters and wall
thicknesses. The nominal diameter of the tubing is expressed in terms of its
Involve the Manufacturer
▲ If provided, use refrigerant
line sizes recommended by
manufacturer
Figure 12
General Piping Requirements
▲ Use clean Type L copper tubing
◆ Copper-to-copper joints: BCuP-6 without flux
◆ Copper-to-steel (or brass) joints: BAg-28, non-acid flux
▲ Properly support piping to account for
expansion, vibration, and weight
▲ Avoid installing piping underground
▲ Test entire refrigerant circuit for leaks
Figure 13
TRG-TRC006-EN 9
period one
Refrigerant Piping Requirements
notes outside diameter. This tubing must be completely free from dirt, scale, and
oxide. New Type L or Type ACR tubing that has been cleaned by the
manufacturer and capped at both ends is recommended for air-conditioning
applications.
The piping system is constructed by brazing copper tubes and fittings together.
When brazing copper-to-copper joints, use BCuP-6* without flux. For copper-tosteel or copper-to-brass joints, use BAg-28* with a non-acid flux.
The refrigerant piping must be properly supported to account for expansion,
vibration, and the total weight of the piping. When a pipe experiences a
temperature change, it is subject to a certain amount of expansion and
contraction. Because the refrigerant piping is connected to the compressor,
vibration forces are transmitted to the piping itself. Finally, the weight of the
refrigerant-filled pipe and fittings must be supported to prevent the pipes from
sagging, bending, or breaking.
Avoid installing refrigerant piping underground. It is very difficult to maintain
cleanliness during installation or to test for leaks. If underground installation is
unavoidable, each line must be insulated separately, and then the lines must be
waterproofed and protected with a hard casing (such as PVC).
After the piping has been installed, the entire refrigeration circuit must be
tested for leaks before it can be charged with refrigerant. This process typically
involves pressurizing the entire piping system with dry nitrogen to examine
each brazed joint for leaks.
Each of these issues is discussed in greater detail in the Trane Reciprocating
Refrigeration Manual.
* Based on the American Welding Society’s (AWS) Specification for Filler
Metals for Brazing and Braze Welding, publication A5.8–1992
10 TRG-TRC006-EN
notes
period two
Suction Line
The first line to be considered is the suction line. Again, this pipe conducts lowpressure refrigerant vapor from the evaporator to the compressor.
Requirements for Sizing and Routing
The diameter of the suction line must be small enough that the resulting
refrigerant velocity is sufficiently high to carry oil droplets, at all steps of
compressor unloading. If the velocity in the pipe is too high, however,
objectionable noise may result. Also, the pipe diameter should be as large as
possible to minimize pressure drop and thereby maximize system capacity and
efficiency.
period two
Suction Line
Refrigerant Piping
Figure 14
suction line
Requirements for Sizing and Routing
▲ Ensure adequate velocity to return oil to
compressor at all steps of unloading
▲ Avoid excessive noise
▲ Minimize system capacity and efficiency loss
Figure 15
TRG-TRC006-EN 11
period two
Suction Line
notes
It may be helpful to compare the old “rules” for selecting the diameter of the
suction line with the newer rules that result from changes in compressor
technology, recent research, and the additional requirement to minimize
system refrigerant charge.
In the past, many suction lines for systems operating with Refrigerant-22 were
sized to ensure that the minimum velocity in a vertical suction riser was more
than 1,000 fpm (5 m/s), and the minimum velocity in a horizontal section was
more than 500 fpm (2.5 m/s). Actually, the minimum allowable velocity in a
suction riser depends on the diameter of the pipe.
The minimum velocity required to carry oil droplets up a vertical riser is higher
for a larger diameter pipe than it is for a smaller diameter pipe. This is due to
the velocity profile of the refrigerant flowing inside the pipe. In a smaller
diameter pipe, the higher-velocity refrigerant is closer to the inner walls of the
pipe than it is in a larger-diameter pipe. For instance, while the minimum
allowable velocity in a 2 1/8 in. (54 mm)-diameter suction riser is approximately
1,000 fpm (5 m/s), the minimum velocity in a 1 1/8 in. (28 mm)-diameter riser is
only 700 fpm (3.6 m/s). While the old minimum-velocity limits were easy to
remember, they may lead to the unnecessary use of double suction risers.
The recommended maximum-velocity limit of 4,000 fpm (20 m/s) has not
changed. A higher velocity inside the suction line may cause objectionable
noise for those nearby.
Another common rule, in a system operating with R-22, was to limit the
pressure drop through the suction line to 3 psi (20 kPa). Although this was often
thought to be a maximum limit, this value was originally intended to be only a
recommendation, or guideline, for minimizing capacity and efficiency loss.
Today, architects and HVAC system design engineers are placing the
components of the refrigeration system farther apart, and this 3 psi (20 kPa)
limit is often overly restrictive. Longer line lengths and the associated higher
pressure drop can be tolerated, assuming that the loss of system capacity and
efficiency is acceptable for the given application. Of course, it is still good
suction line
Sizing “Rules”
minimum velocity
1,000 fpm (5 m/s) based on diameter of riser
for vertical risers
500 fpm (2.5 m/s) percentage of minimum
for horizontal sections riser velocity
maximum velocity
4,000 fpm (20 m/s) 4,000 fpm (20 m/s)
maximum pressure drop
3 psi (20 kPa) based on specific system
requirements
old rules for R-22 new rules for R-22
Figure 16
notes
period two
Suction Line
practice to minimize pressure drop, but an arbitrary limit places an unnecessary
restriction on the system designer.
Sizing Process
Following are the steps to follow when selecting the proper diameter of the
suction line:
1) Determine the total length of suction-line piping.
2) Calculate the refrigerant velocity at both maximum and minimum system
capacities.
3) Select the largest pipe diameter that will result in acceptable refrigerant
velocity at both maximum and minimum capacities.
4) Calculate the total “equivalent” length of piping by adding the actual length
of straight pipe to the equivalent length of any fittings to be installed in the
suction line.
5) Determine the pressure drop (based on the total equivalent length) due to
the straight pipe and fittings.
6) Add the pressure drop due to any accessories installed in the suction line.
To begin with, the refrigerant piping should be routed in the shortest and
simplest manner possible, minimizing the total length of piping. From the initial
layout, the total measured length of the suction line can be estimated.
suction line
Process for Sizing
1 Determine total length of piping
2 Calculate refrigerant velocity at maximum and
minimum capacities
3 Select largest pipe diameter that results in
acceptable velocity at both maximum and
minimum capacities
4 Calculate total equivalent length of straight pipe
and fittings
5 Determine pressure drop due to pipe and fittings
6 Add pressure drop due to accessories
period two
Suction Line
notes
If the system contains more than one independent refrigerant circuit, each
circuit requires its own set of refrigerant lines. Therefore, the capacity of each
individual circuit must be considered separately.
Some refrigeration circuits include only one compressor that cycles on and off.
This is very common in residential and light-commercial air-conditioning
systems. In this case, the refrigeration circuit only operates at one capacity—
fully on—so only the maximum system capacity needs to be considered.
However, if the circuit contains a compressor that is capable of unloading, such
as a single reciprocating compressor with cylinder unloaders, or if more than
one compressor is manifolded together on a single circuit, such as multiple
scroll compressors, then the minimum capacity of the circuit must also be
determined. When the circuit unloads, less refrigerant flows through the
system and the refrigerant velocity inside the piping is reduced.
Recall that the diameter of the suction line must provide adequate velocity at
both maximum and minimum capacities. At maximum capacity, the refrigerant
velocity through the suction line will be the highest. Therefore, maximum
capacity is important to ensure that the refrigerant velocity is below the upper
limit of 4,000 fpm (20 m/s). At minimum capacity, the refrigerant velocity will be
the lowest. Therefore, the minimum capacity of the refrigeration circuit is
critical for ensuring that the refrigerant velocity is high enough to properly
return oil to the compressor.
It is important to note that the diameter of a vertical riser does not necessarily
need to be the same as the diameter of the horizontal or vertical drop sections
of pipe. The horizontal or vertical drop sections can often be selected one
diameter larger than a vertical riser, reducing the overall pressure drop due to
the suction line. This will be demonstrated later in this period.
Unloading Refrigeration Circuits
reciprocating compressor
with cylinder unloaders
scroll compressors
manifolded on a
single circuit

notes
period two
Suction Line
The refrigerant velocity inside a pipe depends on the mass flow rate and
density of the refrigerant, and on the inside diameter of the pipe. The chart in
Figure 19 shows the velocity of R-22 inside pipes of various diameters at one
particular operating condition—40°F (4.4°C) saturated suction temperature,
125°F (51.7°C) saturated condensing temperature, 12°F (6.7°C) of superheat,
15°F (8.3°C) of subcooling, and 70°F (38.9°C) of compressor superheat. For an
example system with an evaporator capacity of 20 tons (70.3 kW), the
refrigerant velocity inside a 2 1/8 in. (54 mm)-diameter pipe at this condition is
about 1,850 fpm (9.4 m/s).
The easiest and most accurate method for determining refrigerant velocity is to
use a computer program that can calculate the velocity for various pipe sizes
based on actual conditions. However, if you do not have access to such a
program, a chart like this may be useful.
Assume that this example 20-ton (70.3-kW) system contains one refrigeration
velocity, fpm (m/s)
evaporator capacity, tons (kW)
R-22
suction line
Determine Refrigerant Velocity
pipe diameter, in. (mm)
Figure 19
suction line
Determine Refrigerant Velocity
pipe velocity, fpm (m/s)
diameter,
in. (mm)
20 tons
(70.3 kW)
10 tons
(35.2 kW)
1 1/8 (28) 7,000 (35.6) 3,500 (17.8)
1 3/8 (35) 4,600 (23.4) 2,300 (11.7)
1 5/8 (42) 3,250 (16.5) 1,625 (8.3)
2 1/8 (54) 1,850 (9.4) 925 (4.7)
2 5/8 (67) 1,200 (6.1) 600 (3.1)
3 1/8 (79) 850 (4.3) 425 (2.2)

period two
Suction Line
notes circuit with two steps of capacity. Maximum system (evaporator) capacity is 20 tons (70.3 kW) and the circuit can unload to 10 tons (35.2 kW) of capacity.
Using the chart in Figure 19 on page 14, the refrigerant velocity at both
maximum and minimum capacities is determined for several pipe diameters.
After these velocities have been determined, the largest acceptable pipe
diameter is selected to minimize the overall pressure drop due to the suction
line.
When this system operates at maximum capacity, use of either the 1 1/8 in.
(28 mm)- or the 1 3/8 in. (35 mm)-diameter pipes results in a refrigerant velocity
that is greater than the recommended upper limit of 4,000 fpm (20 m/s). Again,
these high velocities may cause objectionable noise, so these pipe sizes should
probably not be considered.
Figure 21 shows the minimum allowable refrigerant velocity, for both a vertical
suction riser and a horizontal (or vertical drop) section of suction line, for each
standard pipe diameter. As mentioned earlier in this period, the minimum
allowable velocity in a suction riser depends on the diameter of the pipe. The
minimum velocity for a horizontal, or vertical drop, section is 75 percent of the
minimum allowable velocity for a vertical riser of the same diameter.
The minimum velocities listed in this table assume a worst-case operating
condition of 20°F (-6.7°C) saturated suction temperature. This provides a safety
factor, because a system will probably operate at this type of condition at some
time in its life.

suction line
Minimum Allowable Velocities
Figure 21
16 TRG-TRC006-EN
notes
period two
Suction Line
Based on the minimum allowable velocities listed in Figure 21 on page 15, a
2 1/8 in. (54 mm) pipe will result in acceptable velocity, at both maximum and
minimum capacities, for the horizontal and vertical drop sections of this
example suction line. One size larger would result in a velocity that is too low
when the system operates at minimum capacity.
When the circuit unloads to 10 tons (35.2 kW), however, the velocity inside a
2 1/8 in. (54 mm) pipe—925 fpm (4.7 m/s)—will drop below the minimum
allowable velocity for a vertical riser of this diameter—980 fpm (5.0 m/s).
Downsizing all vertical suction risers to 1 5/8 in. (42 mm)-diameter pipe will
result in acceptable velocity at both maximum and minimum capacities. At
minimum capacity, the velocity—1,625 fpm (8.3 m/s)—is above the minimum
allowable velocity for a riser of this diameter—840 fpm (4.3 m/s). At maximum
capacity, the velocity—3,250 fpm (16.5 m/s)—is below the 4,000 fpm (20 m/s)
upper limit.
Select Suction Line Size
riser horiz/drop
20 (70.3) 1,850 (9.4)
10 (35.2) 925 (4.7)
circuit
capacity, minimum velocity for 2 1/8 in.
(54 mm) pipe, fpm (m/s) velocity inside
2 1/8 in. (54 mm)
tons (kW)
pipe, fpm (m/s)
980 (5.0) 735 (3.7)
riser horiz/drop
20 (70.3) 3,250 (16.5)
10 (35.2) 1,625 (8.3)
circuit
capacity, minimum velocity for 1 5/8 in.
(42 mm) pipe, fpm (m/s) velocity inside
1 5/8 in. (42 mm)
tons (kW)
pipe, fpm (m/s)
840 (4.3) 630 (3.2)
Figure 22
TRG-TRC006-EN 17
period two
Suction Line
notes
For this example system, a 2 1/8 in. (54 mm)-diameter pipe can be used for the
horizontal and vertical drop sections of the suction line, and a 1 5/8 in. (42 mm)-
diameter pipe should be used for the vertical riser. This combination of pipe
sizes will ensure proper oil movement at both maximum and minimum system
capacities, and minimize the overall pressure drop due to the suction line.
This process suggests selecting the largest-possible pipe diameter to minimize
pressure drop. For some applications, however, using a smaller pipe diameter
may be possible and can reduce the installed cost of the system. Of course, the
smaller pipe diameter will result in a higher pressure drop and must meet the
minimum and maximum velocity requirements.
For this example system, for the vertical riser, a single pipe diameter was
selected that provides adequate velocity at minimum capacity without
exceeding the upper velocity limit at maximum capacity. This is generally
possible when the minimum capacity of the refrigeration circuit is not less than
30 to 37 percent of maximum capacity.
Selected Suction Line Sizes
compressor
evaporator
2 1/8 in.
(54 mm)
1 5/8 in. (42 mm)
riser
2 1/8 in.
(54 mm)
drop
Figure 23
18 TRG-TRC006-EN
notes
period two
Suction Line
If the refrigeration circuit unloads to less than 30 to 37 percent of maximum
capacity, a double suction riser may be required.
Using the same example 20-ton (70.3-kW) system, assume that the refrigeration
circuit can, instead, unload to 5 tons (17.6 kW). At this minimum capacity, the
velocity inside the 1 5/8 in. (42 mm) pipe—810 fpm (4.1 m/s)—will drop below
the minimum allowable velocity for a riser of this diameter—840 fpm (4.3 m/s).
Selecting the smaller 1 3/8 in. (35 mm)-diameter pipe for the vertical riser would
result in a velocity that is too high—4,600 fpm (23.4 m/s)—at maximum
capacity.
A double suction riser is constructed of a larger-diameter riser with a trap at the
base and a smaller-diameter riser in parallel. At maximum capacity, the
refrigerant vapor flows up both risers at velocities that are adequate to carry the
oil droplets.
Double Suction Riser
20 (70.3) 3,250 (16.5)
5 (17.6) 810 (4.1)
circuit
capacity,
tons (kW)
minimum velocity for
1 5/8 in. (42 mm) riser,
fpm (m/s)
velocity inside
1 5/8 in. (42 mm)
pipe, fpm (m/s)
840 (4.3)
20 (70.3) 4,600 (23.4)
5 (17.6) 1,150 (5.9)
circuit
capacity,
tons (kW)
minimum velocity for
1 3/8 in. (35 mm) riser,
fpm (m/s)
velocity inside
1 3/8 in. (35 mm)
pipe, fpm (m/s)
780 (4.0)
Figure 24
Double Suction Riser
larger
riser
smaller
riser
trap

period two
Suction Line
notes At minimum capacity, the refrigerant velocity in the two risers becomes too low
to carry the oil droplets. The oil from both risers therefore drains down, filling
the trap at the base of the larger riser. When this trap becomes completely filled
with oil, it prevents refrigerant vapor from flowing up the larger riser, and
diverts all the refrigerant up the smaller riser. This smaller riser is constructed
of a pipe with a diameter that is small enough to maintain adequate velocity at
minimum capacity. When system capacity is increased again, the higher
refrigerant velocity clears the trap of oil, and refrigerant vapor again flows up
both risers.
Notice the inverted trap at the top of the larger riser. When the trap at the base
of the larger riser is filled with oil, and refrigerant flows up only the smaller
riser, this inverted trap prevents oil from draining back into the larger riser. This
configuration minimizes the amount of oil trapped in the double riser under this
condition, therefore maximizing the amount of oil that is returned to the
compressor.
When sizing a double suction riser, the diameter of the smaller riser should be
selected to provide the minimum allowable velocity at minimum capacity. The
diameter of the larger riser should then be selected so that, at maximum
capacity, the velocities in both risers are greater than the minimum allowable
velocity and less than 4,000 fpm (20 m/s).
For this example system, the diameter of the smaller riser is 1 3/8 in. (35 mm).
When the system operates at its minimum capacity of 5 tons (17.6 kW), the
velocity inside the 1 3/8 in. (35 mm) riser—1,150 fpm (5.8 m/s)—is above the
minimum allowable velocity for a riser of this diameter.
At the maximum system capacity of 20 tons (70.3 kW), the smaller riser is
assumed to handle the same 5 tons (17.6 kW) of capacity, and the larger riser
must handle the remaining capacity. At 15 tons (52.8 kW) of capacity, the
refrigerant velocity in a 1 5/8 in. (42 mm) riser—2,450 fpm (12.4 m/s)—is
between the maximum and minimum allowable velocities for a riser of this
diameter.
Sizing a Double Suction Riser
▲ Sizing the smaller riser
▲ Sizing the larger riser
5 (17.6) 1,150 (5.8)
circuit
capacity,
tons (kW)
minimum velocity
for 1 3/8 in. (35 mm)
riser, fpm (m/s)
velocity inside
1 3/8 in. (35 mm)
pipe, fpm (m/s)
780 (4.0)
15 (52.8) 2,450 (12.4)
circuit
capacity,
tons (kW)
minimum velocity
for 1 5/8 in. (42 mm)
riser, fpm (m/s)
velocity inside
1 5/8 in. (42 mm)
pipe, fpm (m/s)
840 (4.3)
notes
period two
Suction Line
For this example system, a 2 1/8 in. (54 mm)-diameter pipe can be used for the
horizontal or vertical drop sections, and the double suction riser should be
constructed using 1 5/8 in. (42 mm)-diameter pipe for the larger riser and
1 3/8 in. (35 mm)-diameter pipe for the smaller riser.
Do not use a double suction riser unless it is absolutely necessary! The double
riser stores a large amount of oil—oil that is preferably left in the crankcase of
the compressor. If a double riser is required, check with the equipment
manufacturer to determine if more oil must be added to the system.
After the pipe diameters are selected, the overall pressure drop due to the
suction line can be calculated. The next step is to calculate the total
“equivalent” length of the suction line. The total equivalent length is the actual
measured length of straight pipe plus the pressure drop through any fittings,
such as elbows and tees. The pressure drop through the fittings is expressed in
terms of the length of straight pipe that would produce the same pressure drop.
To determine the equivalent length of various copper fittings, Trane now uses
the results from two decades of research conducted for the American Society of
Mechanical Engineers (ASME). This research produced a method for predicting
the pressure drop, in terms of equivalent length (Leq), through various types of
copper fittings by using the radius of curvature (r) of the fitting divided by its
diameter (d), or r/d. Table 1 on page 21 includes this data.
Calculate Total Equivalent Length
L
eq is based on r/d
radius of curvature (r)
diameter (d)

period two
Suction Line
notes
The research findings show that the equivalent lengths of copper fittings are
much smaller than the data used in the past. The table in Figure 28 compares
some of the equivalent-length data from this research to the values commonly
used in the past. While this data is for long-radius elbows, the same method is
used to predict the equivalent length of short-radius elbows and tees.
The suction line for this example 20-ton (70.3-kW) system, shown in Figure 23
on page 17, is 70 ft (21.4 m) long. The horizontal and vertical drop sections total
55 ft (16.8 m) in length, and are constructed of 2 1/8 in. (54 mm)-diameter pipe
with three long-radius elbows and three short-radius elbows. The single vertical
riser is 15 ft (4.6 m) long, and is constructed of 1 5/8 in. (42 mm)-diameter pipe
with no fittings.

suction line
Determine Pressure Drop

p2 1/8 in. = = 66.1 ft 1.4 psi/100 ft 0.93 psi
p54 mm = = 20.2 m 3.2 kPa/10 m 6.4 kPa
p1 5/8 in. = = 15 ft 6 psi/100 ft 0.9 psi
p42 mm = = 4.6 m 13.5 kPa/10 m 6.2 kPa

period two
Suction Line
notes Therefore, the total pressure drop through the straight pipe and fittings for this example suction line is 1.83 psi (12.6 kPa).
The final step toward calculating the total pressure drop is to add the pressure
drop due to any accessories that are to be installed in the suction line. The most
common accessories installed in a suction line are a suction filter and manual
ball valves that can be used to isolate this filter when it needs to be replaced.
Assuming that this example system includes one suction filter and two manual
ball valves installed in the 2 1/8 in. (54 mm) line, the total pressure drop due to
the suction line is 3.86 psi (26.6 kPa).
As mentioned earlier, a common rule in the past was to limit the pressure drop
through the suction line to 3 psi (20 kPa) for a system operating with R-22.
However, long line lengths, and the associated higher pressure drops, can be
tolerated assuming that the impact on system capacity and efficiency is
acceptable for the given application.
∆p = = 0.93 psi 0.9 psi + 1.83 psi
∆p = = 6.4 kPa 6.2 kPa + 12.6 kPa
suction line
Add Pressure Drop of Accessories
▲ Suction filter = 2 psi (13.8 kPa)
▲ Angle valve = 1 psi (6.9 kPa)
▲ Ball valve = 1 equivalent ft (0.3 m)
suction line filter
p 1.83 psi 2 psi 2 1 ft = = + + 1.4 psi/10 ft 3.86 psi
p 12.6 kPa 13.8 kPa 2 0.3 m = = + + 3.2 kPa/10 m 26.6 kPa
notes
period two
Suction Line
Other Considerations
Certain precautions should be taken when routing the suction line. First, proper
location and attachment of the remote expansion-valve bulb is very
important. This remote bulb, which measures the temperature of the refrigerant
leaving the evaporator, should be firmly attached to a straight, well-drained,
horizontal section of the suction line. The external equalizer line should be
inserted downstream of the remote bulb, in order to prevent influencing the
temperature measured by the bulb due to any leakage of liquid refrigerant
through the equalizer line.
The section of pipe at the outlet of the evaporator must be long enough to
permit the attachment of the remote bulb and the insertion of the external
equalizer line. A good rule is to allow 12 in. (300 mm) of straight horizontal pipe
for these two connections. Under no circumstances should the remote bulb be
located on a section of pipe where oil or liquid refrigerant could be trapped. The
presence of oil or liquid refrigerant can cause false temperature readings.
Slightly pitch this short horizontal section of pipe downward from the suction
header—1 in./10 ft (10 mm/3 m) in the direction of flow. For best temperature
sensing, the remote bulb should be firmly attached to the top of this section of
pipe and well insulated.
In addition, an access port should be located near the external equalizer line
connection. This port provides a point for accurate pressure measurement
when checking or adjusting the superheat setting of the TXV.
TXV Installation
external equalizer line
remote
bulb
evaporator
TXV
refrigerant
vapor
distributor
liquid
refrigerant

period two
Suction Line
notes
After this short horizontal section, the suction line should drop vertically
downward to allow the evaporator, and the section of pipe with the TXV bulb
attached, to drain freely when the system is operating.
If the suction line leaves the evaporator and then must rise immediately, this
can be accomplished by using a small trap at the end of the horizontal section
of pipe, just before the suction line rises. The purpose of this trap is to provide
free drainage from the evaporator and the section of pipe to which the TXV
bulb is attached. This ensures that the TXV bulb is not the “low spot” in the
piping where oil or liquid refrigerant could be trapped. The purpose of this trap
is not to drain the suction riser.
The suction line must then rise above the height of the evaporator coil. This
prevents refrigerant and oil inside the evaporator from free draining into the
suction line, and toward the compressor, when the system is off.
The configuration in Figure 32 is typical for a system with an indoor air handler,
where the refrigerant piping is routed along the ceiling and must drop down to
the evaporator.
single distributor on circuit
Evaporator Coil Connection
TXV
bulb
must rise above
height of evaporator
must drop below
header outlet
suction header
Figure 32
26 TRG-TRC006-EN
notes
period two
Suction Line
If the suction line leaves the evaporator and then must drop vertically, an
inverted trap is used to prevent refrigerant and oil inside the evaporator from
free draining into the suction line, and toward the compressor, when the
system is off.
This involves piping the suction line to rise above the height of the evaporator
coil, installing an inverted trap, and then allowing the line to drop back down
below the evaporator.
When an evaporator has more than one distributor connected to a single
refrigeration circuit, there are some additional considerations for manifolding
the suction headers into a single suction line.
First, arrange the suction line so that the refrigerant vapor leaving the top
suction header flows downward, connecting to the pipes leaving the other
suction headers. This manifold pipe should drop below the lowest suction
single distributor on circuit
Evaporator Coil Connection
TXV
bulb
must rise above
height of evaporator
must drop below
header outlet
suction header
Figure 33
multiple distributors on circuit
Evaporator Coil Connections
TXV
bulb
must drop below
lowest header outlet double-elbow
configuration
must rise above
height of evaporator
Figure 34
TRG-TRC006-EN 27
period two
Suction Line
notes header outlet before being allowed to turn upward. This allows all of the oil to
drain out of the evaporator and congregate before it must be carried up a
vertical riser.
Second, the remote TXV bulbs and external equalizing line connections must
be located so that the conditions affecting one valve cannot influence the other
valves. The double-elbow configuration allows the corresponding section of the
evaporator coil to drain freely while also isolating the remote bulb and
equalizer line from the suction pressure and temperature of the above coil
sections.
The single suction line then rises above the height of the evaporator coil,
preventing refrigerant and oil inside the evaporator from free draining into the
suction line, and toward the compressor, when the system is off.
As mentioned earlier, the trap shown in Figure 32 on page 25, and Figure 33 on
page 26, is used to provide free drainage from the evaporator and section of
pipe to which the TXV bulb is attached. Its purpose is not to drain the suction
riser.
A common practice in the past was to install a trap at the base of any vertical
suction riser, and often part of the way up the riser. It was believed that these
traps would cause turbulence at the base of the riser section so that oil
accumulating in the trap would be more easily “broken up” into a mist, which
could then be carried to the top of the riser with the refrigerant vapor.
Today, we understand that oil droplets are moved inside a pipe by the force of
mass flow, not by turbulence. It is possible to size a vertical suction riser, which
will allow the refrigerant to carry oil droplets at minimum capacity, without the
need for a trap. If a suction riser is sized properly, oil will return to the
compressor regardless of whether a trap is present at the base of the riser. If a
suction riser is oversized, however, adding such a trap will not restore proper
oil movement.
suction line
Riser Traps Are Not Required

notes
period two
Suction Line
Horizontal sections of the suction line should be pitched slightly—1 in./10 ft
(10 mm/3 m)—so that the refrigerant drains back toward the evaporator. This
prevents any refrigerant that condenses in the suction line from flowing into the
compressor when the circuit is off.
The refrigerant temperature inside the suction line is generally cooler than the
surrounding air. Therefore, it is always good practice to insulate the entire
suction line to prevent condensation and loss of capacity due to heat gain.
Without insulation, moisture may condense on the outside surface of the pipe
and drip onto the floor or suspended ceiling below. Also, any heat gained by
the suction line places an additional load on the system that reduces cooling
capacity, and also may result in improper motor cooling with some compressor
designs.
The suction-line filter should be located as close as possible to the
compressor—its purpose is to remove foreign matter from the system and
protect the compressor. This filter should be accompanied by manual shutoff
valves on both sides, allowing it to be isolated when the filter core needs to be
replaced.
Additionally, the suction line typically includes two access ports. One is
installed near the compressor and is used to measure suction pressure. The
other is located near the external equalizer line connection for the TXV, and is
used to measure superheat when checking or adjusting the TXV.
suction line
Other Considerations
▲ Do not use suction riser traps: they are not
required
▲ Pitch horizontal sections to drain toward
evaporator
▲ Insulate entire suction line
◆ Prevents condensation
◆ Minimizes loss of capacity due to heat gain
▲ Install suction-line filter close to compressor
◆ Manual shutoff valves allow isolation for replacement
▲ Install access ports to measure suction
pressure and superheat
period two
Suction Line
notes
The compressor is designed to compress refrigerant vapor only. A suctionline accumulator is a device that attempts to prevent a slug of liquid
refrigerant or oil from causing damage to the compressor. The accumulator
allows liquid refrigerant and oil to separate from the refrigerant vapor, and then
be drawn into the compressor at a rate that will not cause damage.
Oversizing the accumulator, however, can cause inadequate oil return due to
low refrigerant velocity through the accumulator. An accumulator also
increases the refrigerant charge of the system and increases the pressure drop.
Some refrigeration systems that use a flooded evaporator may require a
suction-line accumulator for freeze protection or other functions. Check with the
equipment manufacturer to determine if a suction-line accumulator is required,
recommended, or discouraged.
Suction-Line Accumulator
▲ Check with
equipment
manufacturer to
determine if required,
recommended, or
discouraged
notes
period two
Suction Line
Finally, when the system includes a reciprocating compressor, an anchored,
45-degree canted loop should be constructed very close to the location at which
the suction line connects to the compressor. This loop absorbs vibration
generated by the reciprocating motion of the compressor, minimizing the
amount of vibration transmitted to the piping system.
The loop is constructed of four straight sections of pipe, each one at least ten
pipe diameters in length, and four elbows. The pipe is anchored a short
distance downstream from the loop, allowing the loop to absorb vibration in
both the vertical and horizontal planes. Note that the loop is pitched downward
to provide free drainage away from the compressor.
suction line
Reciprocating Compressors
pipe
anchor
pitch

notes
period three
Discharge Line
The next line to be considered is the discharge line. This section of pipe
conducts hot, high-pressure refrigerant vapor from the compressor to the
condenser.
The design of the discharge line is probably less critical than that of the suction
line because the refrigerant vapor is at a higher temperature, allowing the oil to
be carried along more easily than in the cooler suction line. Even so, if the
discharge line is not properly sized and installed, reliability or performance
problems can result.
Requirements for Sizing and Routing
Similar to the suction line, the diameter of the discharge line must be small
enough that the resulting refrigerant velocity is sufficiently high to carry oil
droplets, at all steps of compressor unloading. However, if the velocity in the
pipe is too high, it may cause objectionable noise.
period three
Discharge Line
Refrigerant Piping
Figure 39
discharge line
Requirements for Sizing and Routing
▲ Ensure adequate velocity to return oil to
compressor at all steps of unloading
▲ Avoid excessive noise
▲ Minimize efficiency loss
notes
period three
Discharge Line
Finally, anything that causes the compressor discharge pressure to rise causes
the compressor to work harder. Therefore, the pipe diameter should be as large
as possible to minimize pressure drop and maximize compressor efficiency.
As with the suction line, it may be helpful to compare the old “rules” for
selecting the diameter of the discharge line with the newer rules that result
from changes in compressor technology, recent research, and the additional
requirement to minimize system refrigerant charge.
In the past, many discharge lines for systems operating with R-22 were sized
using the same minimum-velocity values that were used for sizing suction
lines. As explained in Period Two, the minimum allowable velocity at a specific
operating condition depends on the diameter of the pipe. The minimum
allowable velocity values for discharge lines are different than for suction lines,
because the refrigerant vapor is at a higher temperature, and oil moves more
easily than in the cooler suction line.
The recommended maximum velocity limit for discharge lines is 3,500 fpm
(17.5 m/s). Again, a higher velocity inside the pipe may cause objectionable
noise.
Another “old” rule, for a system operating with R-22, was to limit the pressure
drop through the discharge line to 6 psi (41 kPa). While it is still good practice to
minimize pressure drop, higher pressure drops can be tolerated, assuming that
the impact on system efficiency is acceptable for the given application.
discharge line
Sizing “Rules”
minimum velocity
1,000 fpm (5 m/s) based on diameter of riser
for risers
500 fpm (2.5 m/s) percentage of minimum
for horizontal sections riser velocity
maximum velocity
3,500 fpm (17.5 m/s) 3,500 fpm (17.5 m/s)
maximum pressure drop
6 psi (41 kPa) based on specific system
requirements
old rules for R-22 new rules for R-22
period three
Discharge Line
notes
Sizing Process
The steps for selecting the proper diameter of the discharge line are identical to
the steps for sizing the suction line:
1) Determine the total length of discharge-line piping.
2) Calculate the refrigerant velocity at both maximum and minimum system
capacities.
3) Select the largest pipe diameter that will result in acceptable refrigerant
velocity at both maximum and minimum capacities.
4) Calculate the total “equivalent” length of piping by adding the actual length
of straight pipe to the equivalent length of any fittings to be installed in the
discharge line.
5) Determine the pressure drop (based on the total equivalent length) due to
the straight pipe and fittings.
6) Add the pressure drop due to any accessories installed in the discharge
line.
Again, the total measured length of the discharge line can be estimated from
the initial layout.
discharge line
Process for Sizing
1 Determine total length of piping
2 Calculate refrigerant velocity at maximum and
minimum capacities
3 Select largest pipe diameter that results in
acceptable velocity at both maximum and
minimum capacity
4 Calculate total equivalent length of straight pipe
and fittings
5 Determine pressure drop due to pipe and fittings
6 Add pressure drop due to accessories
notes
period three
Discharge Line
The chart in Figure 43 shows the velocity of R-22 inside discharge pipes of
various diameters at one particular operating condition—40°F (4.4°C) saturated
suction temperature, 125°F (51.7°C) saturated condensing temperature, 12°F
(6.7°C) of superheat, 15°F (8.3°C) of subcooling, and 70°F (38.9°C) of
compressor superheat.
For the same example 20-ton (70.3-kW) system, the refrigerant velocity inside a
1 5/8 in. (42 mm)-diameter pipe is about 1,100 fpm (5.6 m/s) at this condition.
Again, a computer program can be used to calculate the velocity based on
actual conditions, but without a program, a chart like this may be useful.
This example 20-ton (70.3-kW) system contains one refrigeration circuit with
two steps of capacity. Maximum capacity is 20 tons (70.3 kW) and minimum
capacity is 10 tons (35.2 kW). Using the chart in Figure 43, the refrigerant
discharge line
Determine Refrigerant Velocity
velocity, fpm (m/s)
evaporator capacity, tons (kW)
pipe diameter, in. (mm)

discharge line
Determine Refrigerant Velocity
7/8 (22) 4,050 (20.6) 2,025 (10.3)
1 1/8 (28) 2,400 (12.2) 1,200 ( 6.1)
1 3/8 (35) 1,550 ( 7.9) 775 ( 3.9)
1 5/8 (42) 1,100 ( 5.6) 550 ( 2.8)
2 1/8 (54) 650 ( 3.3) 325 ( 1.7)
pipe velocity, fpm (m/s)
diameter,
in. (mm)
20 tons
(70.3 kW)
10 tons
(35.2 kW)
period three
Discharge Line
notes velocity at both maximum and minimum capacities is determined for several
pipe diameters.
After these velocities have been determined, the largest acceptable pipe
diameter is selected to minimize the overall pressure drop due to the discharge
line.
When this system operates at maximum capacity, use of the 7/8 in. (22 mm)-
diameter pipe results in a refrigerant velocity that is greater than the
recommended upper limit of 3,500 fpm (17.5 m/s) for discharge lines. This high
velocity may cause objectionable noise, so this pipe size should probably not
be considered.
The table in Figure 45 shows the minimum allowable refrigerant velocity, for
both a vertical riser and a horizontal (or vertical drop) section of discharge line,
for each standard pipe diameter. As with suction lines, the minimum velocity
for a horizontal, or vertical drop, section of discharge line is 75 percent of the
minimum allowable velocity for a vertical riser of the same diameter.
The minimum velocities listed in this table assume a worst-case operating
condition of 80°F (26.7°C) saturated condensing temperature.
discharge line
Minimum Allowable Velocities
period three
Discharge Line
Based on the minimum allowable velocities listed in Figure 45 on page 35,
1 5/8 in. (42 mm) is the largest diameter of pipe that will result in acceptable
velocity, at both maximum and minimum capacities, within horizontal and
vertical drop sections.
When the circuit unloads to 10 tons (35.2 kW), the velocity inside a 1 5/8 in.
(42 mm) pipe—550 fpm (2.8 m/s)—remains above the minimum allowable
velocity for a riser of this diameter—520 fpm (2.6 m/s). One size larger (2 1/8 in.
[54 mm]) would result in a velocity that is too low when the system operates at
minimum capacity.
For this example system, a 1 5/8 in. (42 mm)-diameter pipe can be used for all
horizontal and vertical sections of the discharge line, including vertical risers.
This pipe size will ensure proper oil movement at both maximum and minimum
system capacities, and minimize the overall pressure drop due to the discharge
line.
Select Discharge Line Size
riser horiz/drop
20 (70.3) 1,100 (5.6)
10 (35.2) 550 (2.8)
tons (kW)
pipe, fpm (m/s)
520 (2.6) 390 (2.0)
Selected Discharge Line Size
1 5/8 in.
(42 mm)
compressor
condenser
1 5/8 in. (42 mm)
riser
1 5/8 in.
(42 mm)

period three
Discharge Line
notes For this example, a single pipe diameter can be selected that provides adequate
velocity at minimum capacity, without exceeding the maximum velocity limit at
maximum capacity. If the maximum and minimum velocity requirements
cannot be achieved with a single pipe diameter, a double riser may be required.
After the pipe diameter is selected, the overall pressure drop due to the
discharge line can be calculated. The next step is to calculate the total
“equivalent” length of the straight pipe and fittings. The equivalent length data
for copper fittings used in the discharge line is the same as for the suction line.
The discharge line for this example 20-ton (70.3-kW) system, shown in
Figure 47 on page 36, is a total of 50 ft (15.2 m) long. Both the horizontal
sections and the vertical riser are constructed of 1 5/8 in. (42 mm)-diameter pipe
and contain a total of two long-radius elbows. Based on the “new” data from
Table 1 on page 21, the equivalent length of each long-radius elbow of this
diameter is 1.0 ft (0.30 m), so the total equivalent length of the discharge line is
52 ft (15.8 m).
The next step is to determine the pressure drop due to the straight pipe and
fittings, based on this calculated total equivalent length. The chart in Figure 48
shows the pressure drop, per unit of equivalent length, for different pipe
diameters and various capacities. At the maximum capacity of 20 tons
(70.3 kW), the pressure drop due to the straight, 1 5/8 in. (42 mm)-diameter pipe
and fittings is 2.1 psi per 100 ft of equivalent length (4.8 kPa/10 m), or 1.1 psi
(7.6 kPa).

discharge line
Determine Pressure Drop
period three
Discharge Line
The final step is to add the pressure drop due to any accessories that will be
installed in the discharge line, and calculate the total pressure drop. The most
common accessories installed in a discharge line are manual ball valves that
are used to isolate portions of the system during maintenance.
Assuming that this example system includes one manual angle valve, the total
pressure drop due to the discharge line is 2.1 psi (14.5 kPa).
As mentioned earlier, in the past, a common rule was to limit the pressure drop
through the discharge line to 6 psi (41 kPa) for a system operating with R-22.
However, long line lengths, and the associated higher pressure drops, can be
tolerated assuming that the impact on system efficiency is acceptable for the
given application.
discharge line
Add Pressure Drop of Accessories
▲ Angle valve = 1 psi (6.9 kPa)
▲ Ball valve = 1 equivalent ft (0.3 m)
period three
Discharge Line
Other Considerations
As with the suction line, riser traps are not required in a discharge line,
assuming that the riser is properly sized to return oil at minimum capacity.
Horizontal sections of the discharge line should be pitched slightly—1 in./10 ft
(10 mm/3 m)—so that the refrigerant drains toward the condenser. This
prevents any refrigerant that may condense in the discharge line from flowing
back into the compressor when the system is off.
In most cases, the discharge line does not need to be insulated. The refrigerant
temperature inside the line is generally warmer than the surrounding air. Any
heat loss reduces the heat-rejection load of the condenser, improving system
efficiency. However, the outer surface of the discharge line can be hot. Some
sections of the discharge line may be insulated to prevent injury to someone
who may come in contact with the piping. Also, if the system has long
refrigerant lines and is expected to operate when it is cold outdoors, the
discharge line should be insulated to prevent refrigerant from condensing
inside the line before it reaches the condenser.
discharge line
Other Considerations
▲ Do not use discharge riser traps: they are not
required
▲ Pitch horizontal sections to drain toward
condenser
▲ Insulate only to prevent accidental burns or
when system must operate in cold ambient
conditions
period three
Discharge Line
Finally, when the system includes a reciprocating compressor, an anchored,
45-degree canted loop should be constructed very close to the location at which
the discharge line connects to the compressor. This loop absorbs vibration
generated by the reciprocating motion of the compressor. Note that the loop is
pitched downward to provide free drainage away from the compressor.
discharge line
Reciprocating Compressors
pipe
anchor
pitch
period four
Liquid Line
The third line to be considered is the liquid line. This section of pipe conducts
warm, high-pressure liquid refrigerant from the condenser to the expansion
device and evaporator.
Requirements for Sizing and Routing
The liquid line must be designed and installed to ensure that only liquid
refrigerant (no vapor) enters the expansion device. The presence of refrigerant
vapor upstream of a TXV can result in erratic valve operation and reduced
system capacity. In order to meet this requirement, the condenser must provide
adequate subcooling, and the pressure drop through the liquid line and
accessories must not be high enough to cause flashing upstream of the
expansion device. Subcooling allows the liquid refrigerant to experience some
pressure drop as it flows through the liquid line, without the risk of flashing.
period four
Liquid Line
Refrigerant Piping
Figure 52
liquid line
Requirements for Sizing and Routing
▲ Ensure that only liquid refrigerant enters
expansion device
▲ Minimize refrigerant charge
▲ Avoid excessive noise and pipe erosion
period four
Liquid Line
Oil and liquid refrigerant mix readily, so oil movement within the liquid line is
not a concern. However, the design of the liquid line is the most critical when it
comes to minimizing the system refrigerant charge. This is because, of the
three lines, it has the greatest impact on the quantity of refrigerant required to
charge the system. The diameter of the liquid line must be as small as possible
to minimize the refrigerant charge, therefore improving reliability and
minimizing installed cost. However, if the pipe is too small, the increased
pressure drop may cause flashing upstream of the expansion device.
The final requirement is to limit the refrigerant velocity in order to prevent
objectionable noise or erosion of the inner surfaces of the piping.
In this example system, the refrigerant (R-22) is condensed at a temperature of
125°F (51.7°C), which corresponds to a pressure of 293 psia (2,020 kPa). Inside
the subcooling tubes, the temperature of the liquid refrigerant is reduced by
15°F (8.3°C) to 110°F (43.3°C). Ignoring the pressure drop due to the condenser
and subcooler tubes, the pressure of this subcooled liquid refrigerant is the
same, 293 psia (2,020 kPa).
At 110°F (43.3°C), the pressure of the refrigerant can be reduced to 241 psia
(1,662 kPa) before it reaches the saturated liquid condition, where flashing
occurs. In other words, the liquid refrigerant could experience a pressure drop
of up to 52 psi (358 kPa) before flashing occurs.
In years past, the liquid line was considered an independent component of the
system and was sized based solely on the physics of fluid flow through the
pipe. It was believed that increasing the diameter of the liquid line, which would
reduce the pressure drop through the piping, would increase the amount of
subcooling remaining at the inlet of the expansion device.
The internal volume of the liquid line, however, has a significant impact on the
ability of the condenser to provide subcooling at part-load operating
conditions. When this interaction between the liquid line and condenser is
considered, we find that the amount of subcooling available at the expansion
device is as dependent on the ability of the condenser to provide subcooling as
Subcooling
enthalpy, Btu/lb (kJ/kg)
period four
Liquid Line
it is on the pressure drop due to the liquid-line piping. In fact, if the liquid line is
too large, it will actually reduce the subcooling at the expansion device under
cooler ambient conditions.
Therefore, proper sizing of the liquid line requires an understanding of the
entire refrigeration system, not just the liquid-line piping.
Take a look at an example 25-ton (87.9-kW) system with 150 ft (45.7 m) of liquidline piping to illustrate this point. System A uses a 7/8 in. (22 mm)-diameter
pipe for the liquid line, while system B uses a larger 1 1/8 in. (28 mm)-diameter
pipe. Both systems are charged so that the condenser provides 18°F (10°C) of
subcooling at the same high outdoor temperature. Even though the rest of the
system components are identical, system B requires 25 lb (11.3 kg) more
refrigerant to charge the system because of the larger liquid line.
As expected, the pressure drop due to the piping is less for system B with the
larger diameter pipe. When the outdoor temperature is high, this reduced
pressure drop results in more subcooling remaining at the expansion device—
14.2°F (7.9°C) compared to 12.3°F (6.8°C) for system A.
However, one should examine what happens when the system operates at a
cooler outdoor temperature. As the outdoor temperature decreases, the
temperature of the refrigerant inside the condenser and liquid line also
decreases. This lower temperature causes the density of the refrigerant to
increase, requiring more mass of refrigerant in order to fill up the internal
volume of the liquid line. The result is less refrigerant remaining inside the
condenser, and therefore less subcooling provided by the condenser.
This change in density has a more severe impact on system B with the largerdiameter liquid line, because the internal volume of the liquid line is greater. For
these two example systems, when the outdoor temperature is cooler, the
amount of subcooling provided by the same condenser is 12.9°F (7.2°C) for
system A, but only 7.2°F (4°C) for system B.
Even though the pressure drop is still less through the larger-diameter line—
5.2°F (2.9°C) loss in subcooling due to pressure drop in system B versus 7.4°F
Impact of Refrigerant Density Change
A 7/8 (22) high 18.0 (10) - 5.7 (3.2) = 12.3 (6.8)
B 1 1/8 (28) high 18.0 (10) - 3.8 (2.1) = 14.2 (7.9)
A 7/8 (22) low 12.9 (7.2) - 7.4 (4.1) = 5.5 (3.1)
B 1 1/8 (28) low 7.2 (4.0) - 5.2 (2.9) = 2.0 (1.1)
available subcooling, °F (°C)
liquid line
diameter,
in. (mm)
period four
Liquid Line
(4.1°C) in system A—the impact of the change in refrigerant density has a
greater impact on the overall system. At this cooler outdoor condition, only
2.0°F (1.1°C) of subcooling is available at the TXV in system B, while 5.5°F
(3.1°C) of subcooling is available at the TXV in system A.
Again, proper sizing of the liquid line requires an understanding of the entire
refrigeration system, not just the liquid-line piping. The diameter of the liquid
line should be as small as possible, to minimize the impact of the change in
refrigerant density. If the liquid line is too large, it may result in too little
subcooling at some part-load operating conditions.
Figure 56 compares the old “rules” for selecting the diameter of the liquid line
with the newer rules that result from this understanding of the impact of
refrigerant density change, recent research, and the additional requirement to
minimize system refrigerant charge.
In the past, many liquid lines in systems operating with R-22 were sized to limit
the pressure drop through the piping and accessories to 6 psi (41 kPa).
However, as we just explained, limiting the pressure drop through the liquid
line does not necessarily ensure that only liquid refrigerant (no vapor) enters
the expansion device. This rule has been rewritten to specify that adequate
subcooling must be available at the inlet of the expansion device at all
operating conditions, acknowledging this interaction between the liquid line
and condenser. The condenser must provide adequate subcooling, and the
pressure drop through the liquid line and accessories must not be high enough
to cause flashing upstream of the expansion device. A margin of safety, such as
5°F (2.8°C), may be used to account for unexpected variations.
In the past, the recommended maximum velocity limit for a liquid line was
360 fpm (1.8 m/s). Velocities in excess of this limit caused concern for liquidhammer effect when the flow of refrigerant was suddenly stopped, such as
when a solenoid valve closed. However, most solenoid valves used in airconditioning systems today are not quick-closing valves. That is, they do not
close rapidly enough to cause a serious hammer effect.
liquid line
Sizing “Rules”
maximum pressure drop
6 psi (41 kPa) 5°F (2.8°C) subcooling
remaining at inlet to expansion
device at all operating conditions
maximum velocity
360 fpm (1.8 m/s) 600 fpm (3 m/s)
old rules for R-22 new rules for R-22

period four
Liquid Line
The new maximum-velocity limit of 600 fpm (3 m/s) is based on preventing
erosion of the inner surfaces of the pipe.
Sizing Process
Following are the steps to follow when selecting the proper diameter of the
liquid line:
1) Determine the total length of liquid-line piping.
2) Obtain the amount of subcooling provided by the condenser from the
manufacturer.
3) Determine the refrigerant velocity at maximum system capacity.
4) Select the smallest pipe diameter that will result in acceptable refrigerant
velocity at maximum system capacity.
5) Calculate the total equivalent length of piping by adding the actual
measured length of straight pipe to the equivalent length of any fittings to
be installed in the liquid line.
6) Determine the pressure drop (based on the total equivalent length) due to
the straight pipe and fittings.
7) Add the pressure drop due to any accessories installed in the liquid line.
8) Calculate the loss of subcooling due to pressure drop and to any change in
elevation, to verify adequate subcooling at the inlet to the expansion
device.
From the initial layout, the total measured length of the liquid line can be
estimated. Again, the refrigerant piping should be routed in the shortest and
simplest manner possible, minimizing the total length of piping.
liquid line
Process for Sizing
1 Determine total length of piping
2 Obtain subcooling provided by condenser
3 Determine refrigerant velocity
4 Select smallest pipe diameter that results in
acceptable velocity at maximum capacity
5 Calculate total equivalent length of pipe and fittings
6 Determine pressure drop due to pipe and fittings
7 Add pressure drop due to accessories
8 Calculate loss of subcooling due to pressure drop
and elevation change 
period four
Liquid Line
The next step is to determine how much subcooling is provided by the
condenser. This is difficult because the amount of subcooling provided by an
air-cooled condenser depends on many factors, including the total amount of
heat that must be rejected, the outdoor dry-bulb temperature, the internal
volume of the liquid line, and the system refrigerant charge.
To demonstrate, look at an example operating envelope for a system comprised
of an air-cooled condensing unit (compressors and condenser packaged
together) and a cooling coil (evaporator). The operating envelope is the entire
range of cooling loads for the system over the entire range of outdoor
temperatures at which the system will be operating. Identifying the extreme
corners of this system operating envelope helps us to understand how the
amount of subcooling provided by the condenser varies.
In Figure 58, two of the lines depict the performance of the condensing unit
operating over a range of cooling loads. One line assumes that the unit
operates at a constant high outdoor-air (outdoor or OA) temperature, while the
other line assumes that the same unit operates at a constant low outdoor
temperature.
The other two lines depict the performance of the evaporator coil operating
over a range of outdoor-air temperatures. One line assumes that the coil
operates with a constant high cooling load, while the other line assumes that
the same coil operates with a constant low cooling load.
System Operating Envelope
saturated suction temperature
condensing unit,
high OA temperature
condensing unit,
low OA temperature
evaporator,
high cooling load
evaporator,
low cooling load
system cooling capacity
period four
Liquid Line
This operating envelope defines four extreme corners. Condition A depicts the
system operating with a high cooling load at a high outdoor temperature, and
condition B depicts a low cooling load at the same high outdoor temperature.
Condition C depicts the system operating with a low cooling load at a low
outdoor temperature, and condition D depicts a high cooling load at the same
low outdoor temperature.
A common belief is that the amount of subcooling provided by the condenser
increases when the outdoor temperature is cooler. But this is not necessarily
true in systems that use a TXV for the expansion device. Figure 60 shows how
subcooling changes throughout the operating envelope of an example system.
When the system operates with a high cooling load and a high outdoor
temperature (A), the condenser provides 18°F (10°C) of subcooling. When
operating with the low cooling load at the same high outdoor temperature (B),
less heat must be rejected by the condenser, allowing it to provide more
subcooling—21°F (11.7°C).
System Operating Envelope
high cooling load,
high OA temperature
A
B
D
C
high cooling load,
low OA temperature
low cooling load,
high OA temperature
low cooling load,
low OA temperature
saturated suction temperature
system cooling capacity
Figure 59
effect of cooling load and outdoor temperature
Subcooling Leaving Condenser
A high high 18 (10.0)
B low high 21 (11.7)
C low low 13 (7.2)
D high low 5 (2.8)
subcooling leaving
condenser*, °F (°C)
cooling
load
outdoor
temperature
* This example system uses a TXV for the expansion device.
Figure 60
48 TRG-TRC006-EN
notes
period four
Liquid Line
When the system operates with the low cooling load at a low outdoor
temperature (C), the impact of the refrigerant density change reduces the
subcooling provided by the condenser to 13°F (7.2°C). Finally, when the system
operates with the high cooling load at the same low outdoor temperature (D),
subcooling drops to 5°F (2.8°C). At condition D, the mass flow rate of
refrigerant is high due to the high cooling load, and the refrigerant density is
high due to the low outdoor temperature. This results in very little liquid
refrigerant remaining in the condenser for subcooling.
The key points here are that the amount of subcooling provided by the
condenser changes within the operating envelope, and this subcooling is
actually reduced at cooler outdoor temperatures due to the change in
refrigerant density. This example demonstrates that the condenser provides the
smallest amount of subcooling when the system is operating with a high
evaporator load at a low outdoor temperature.
Defining the operating envelope for a particular system is no easy task, and
therefore is generally not done for each project. Determining the amount of
subcooling provided by the condenser throughout an operating envelope is
also quite complicated. It requires a model of the entire refrigeration system
and help from the manufacturer of the condenser. Therefore, if the
manufacturer of the refrigeration equipment provides recommended line sizes,
or tools for selecting the optimal line sizes, we suggest that you use them.
If recommended line sizes are not provided, however, consult the manufacturer
to determine the amount of subcooling provided by the condenser. For this
example, we will assume 15°F (8.3°C) of subcooling is provided by the
condenser.
Involve the Manufacturer
▲ If provided, use refrigerant
line sizes recommended by
manufacturer
Figure 61
TRG-TRC006-EN 49
period four
Liquid Line
notes
The chart in Figure 62 shows the velocity of liquid R-22 inside liquid lines of
various diameters at one particular operating condition—40°F (4.4°C) saturated
suction temperature, 125°F (51.7°C) saturated condensing temperature, 12°F
(6.7°C) of superheat, 15°F (8.3°C) of subcooling, and 70°F (38.9°C) of
compressor superheat.
For the same example 20-ton (70.3-kW) system, the refrigerant velocity inside a
5/8 in. (15 mm)-diameter pipe is about 520 fpm (2.6 m/s) at this condition.
Again, a computer program can be used to calculate the velocity based on
actual conditions, but without a program, a chart like this may be useful.
Using the chart in Figure 62, the refrigerant velocity at maximum system
capacity—20 tons (70.3 kW), for this example—is determined for various pipe
diameters. Use of the 1/2 in. (12 mm)-diameter pipe results in a refrigerant

liquid line
period four
Liquid Line
velocity that is greater than the recommended upper limit of 600 fpm (3 m/s) for
liquid lines, so it should probably not be considered.
After the velocity inside pipes of various diameters has been determined, the
smallest acceptable pipe diameter is selected to minimize the system
refrigerant charge. The table in Figure 63 on page 49 shows that 5/8 in. (15 mm)
is the smallest diameter of pipe that will result in a velocity below the
recommended upper limit of 600 fpm (3 m/s).
The next step is to calculate the total equivalent length by adding the actual
measured length of straight pipe to the equivalent length of any fittings to be
installed in the liquid line. The equivalent length data for copper fittings used in
the liquid line is the same as for the suction and discharge lines.
The liquid line for this example 20-ton (70.3-kW) system, shown in Figure 64, is
100 ft (30.5 m) long. It is constructed entirely of 5/8 in. (15 mm)-diameter pipe
and contains a total of four long-radius elbows. Based on the “new” equivalent
length data from Table 1 on page 21, the equivalent length of each elbow of this
diameter is 0.4 ft (0.12 m). The total equivalent length of this example liquid line
is calculated to be 101.6 ft (31.0 m).
liquid line
Calculate Total Equivalent Length
evaporator
condenser
period four
Liquid Line
The next step is to determine the pressure drop due to the straight pipe and
fittings, based on the calculated total equivalent length. The chart in Figure 65
shows the pressure drop, per unit of equivalent length, for different pipe
diameters and capacities. This chart is based on one specific operating
condition, but is likely to be representative of the condition when the system
operates at maximum capacity. Alternatively, a computer program can be used
to determine pressure drop at specific conditions.
At the maximum capacity of 20 tons (70.3 kW), the pressure drop due to the
straight pipe and fittings of the liquid line is 17 psi per 100 ft of equivalent
length (72.2 kPa/10 m), or 17.3 psi (119 kPa).
liquid line
Determine Pressure Drop
period four
Liquid Line
The next step is to add the pressure drop due to any accessories that will be
installed in the liquid line, and calculate the total pressure drop. The most
common accessories installed in a liquid line are a filter-drier, a sight glass, a
solenoid valve, and manual ball valves that are used to isolate portions of the
system during maintenance, such as when replacing the core of the filter-drier.
The pressure drop for the filter-drier, shown in Figure 66, assumes that it is
properly sized but dirty.
Assuming that this example system includes a filter-drier, solenoid valve, sight
glass, and two ball valves, the total pressure drop due to the liquid line is
27.8 psi (191 kPa).
liquid line
Add Pressure Drop of Accessories
▲ Filter-drier = 6 psi (41.4 kPa)
▲ Solenoid valve = 4 psi (27.6 kPa)
▲ Sight glass = 1 equivalent ft (0.3 m)
▲ Angle valve = 1 psi (6.9 kPa)
▲ Ball valve = 1 equivalent ft (0.3 m)
solenoid
valve
period four
Liquid Line
The next step is to calculate the loss of subcooling due to the liquid-line
pressure drop and any elevation change.
When the condenser is at a lower elevation than the evaporator, the refrigerant
must overcome the pressure due to a column of liquid refrigerant when flowing
up to the evaporator. This liquid column causes a pressure drop that results in a
decrease in the amount of subcooling available at the expansion device. When
the condenser is at a higher elevation than the evaporator, however, the liquid
column causes a pressure gain that results in an increase in subcooling.
Most systems will include some vertical risers and some vertical drops in the
liquid line, but the critical distance is net elevation difference. For example, the
liquid line in this example system (Figure 67) rises 15 ft (4.6 m) and then later
drops 11 ft (3.4 m). The vertical rise will cause a pressure drop and the vertical
drop will cause a pressure gain, but the net effect of these two vertical sections
will be 4 ft (1.2 m) of rise.
liquid line
Pressure Drop Due to Elevation
evaporator
condenser
15 ft (4.6 m)
vertical rise
creates
pressure drop
11 ft (3.4 m)
vertical drop
creates
pressure gain
period four
Liquid Line
The chart in Figure 68 shows that the magnitude of the associated pressure
drop (or gain) depends primarily on the temperature (density) of the liquid
refrigerant. The greatest pressure drop (or gain) due to this vertical column of
liquid occurs when the temperature of the liquid refrigerant is the lowest.
Using the example liquid line in Figure 67 on page 53, and assuming a liquidrefrigerant temperature of 110°F (43.3°C), the pressure drop due to the 4 ft (1.2
m) net liquid-line rise is 1.9 psi (13.4 kPa).
As you can see, the effect of this liquid column of refrigerant can dramatically
affect the amount of subcooling available at the expansion device, especially at
cooler ambient conditions when the condenser is already providing less
subcooling than it could under design conditions. In fact, it may even use up all
of the subcooling provided by the condenser, resulting in no subcooling
remaining at the expansion device.
Historically, the rule-of-thumb has been to assume a pressure drop of 0.5 psi for
each foot (11.3 kPa/m) of net liquid-line rise.
liquid line
Pressure Drop Due to Elevation

period four
Liquid Line
Next, the pressure drop due to the elevation change is added to the frictional
pressure drop due to the straight pipe, fittings, and accessories. For our
example 20-ton (70.3-kW) system, the total pressure drop due to all of these
effects is 29.7 psi (204.4 kPa).
Then, using the chart in Figure 69, this total pressure drop is converted to an
equivalent loss in subcooling. Assuming a liquid refrigerant temperature of
110°F (43.3°C), the loss of subcooling is 3 psi/°F (37.3 kPa/°C), or 9.9°F (5.5°C).
liquid line
period four
Liquid Line
The last step is to verify that adequate subcooling is available at the inlet to the
expansion device. This involves subtracting the impact of pressure drop and
elevation difference from the amount of subcooling provided by the condenser.
At this condition, 5.1°F (2.8°C) of subcooling is remaining at the inlet to the
expansion device. This is above the minimum limit of 5°F (2.8°C).
As mentioned earlier, in the past, a common rule was to limit the pressure drop
through the liquid line to 6 psi (41 kPa) for a system operating with R-22.
However, as this example demonstrates, in many cases a much higher pressure
drop can be tolerated and allows the liquid line to be smaller. This reduces the
refrigerant charge, which improves system reliability and lowers the installed
cost.
Subcooling Remaining at
Expansion Device

subcooling remaining at expansion device 15 = = F 9.9 – F 5.1F
subcooling remaining at expansion device 8.3 = = C 5.5 – C 2.8C
period four
Liquid Line
Other Considerations
When an evaporator has more than one distributor connected to a single
refrigeration circuit, the liquid line should be designed and installed to provide
equal inlet pressures to the distributors.
In this example, the liquid line is split and the same sizes and lengths of piping
are used to make the connections to the expansion devices and distributors.
This equalizes the pressure drops of the two connections and provides the
most-balanced expansion-device performance.
For proper refrigerant distribution into the evaporator coil, one TXV is required
for each distributor.
A sight glass is installed as close as practical, upstream of the expansion
device. This is a fitting that contains a glass window through which the
refrigerant entering the expansion device may be viewed and its state
liquid line
Evaporator Coil Connections
TXV
distributor
evaporator
solenoid
valve
liquid line
Refrigerant Accessories
sight
glass
TXV
liquid line
solenoid
valve
filter-drier
period four
Liquid Line
determined. As mentioned earlier, flashing of refrigerant upstream of the
expansion device is undesirable. A sight glass can be used to indicate that this
problem exists.
A solenoid-operated shutoff valve is typically installed in the liquid line to
facilitate system pumpdown or to prevent refrigerant migration when the
system is off. Solenoid valves may also be used to control the flow of liquid
refrigerant to multiple sections of the evaporator. In this application, a valve
would be installed upstream of the TXV for each individually controlled section
of the evaporator coil.
A liquid line filter-drier should be installed upstream of, and as close as
possible to, the solenoid valve and TXV. The filter-drier prevents moisture and
foreign matter, introduced during the installation process, from damaging the
solenoid valve or TXV. Manual ball valves should be installed for isolating the
filter-drier when the core needs to be replaced. It is important to realize that the
filter-drier is not a cure-all for poor installation practice. The piping must be
clean, and any air or moisture must be thoroughly evacuated from the system.
Finally, an access port is typically installed in the liquid line in a convenient
location and is used to charge the system with liquid refrigerant. It is also used
to measure the amount of subcooling in the system.
How the liquid line is routed can be important, particularly when the condenser
is located below the evaporator. As an example, the upper system in Figure 73
routes the liquid-line riser before a long horizontal run. The lower system
routes the riser after a long horizontal run.
In both cases, when the refrigeration circuit shuts off, the liquid refrigerant
inside the vertical riser will drain back into the condenser. In the upper system,
however, some of the liquid refrigerant from inside the horizontal run will also
drain back into the condenser. If this quantity of refrigerant is large enough, it
will fill the condenser and overflow into the discharge line and then into the
compressor. This can result in compressor lubrication problems, system
shutdown due to activation of a protective safety device, or mechanical failure.
Liquid Line Routing
period four
Liquid Line
Alternatively, a check valve can be installed in the liquid line, near the outlet of
the condenser, whenever the liquid line rises above the height of the condenser.
This check valve will prevent liquid refrigerant from draining back into the
condenser when the system is off.
A pressure-relief valve is required if both a check valve and a solenoid valve are
installed in the same liquid line. When the refrigeration circuit is off, these two
valves trap liquid refrigerant between them. The pressure-relief valve is
required to relieve the increased pressure that can result when the temperature
of this trapped refrigerant increases.
Generally, horizontal sections of the liquid line should be pitched to run
alongside of the accompanying suction or discharge line. This simplifies the
installation of the line set. Sloping the liquid line in one direction will not always
prevent the flow of refrigerant in the opposite direction because it may move
due to the siphon effect.
The refrigerant temperature inside the liquid line is generally higher than that of
the surrounding air. Therefore, insulation is not typically required. In fact, heat
loss may be desirable because it provides additional subcooling. If the liquid
line is routed through areas that are significantly warmer than the liquid
refrigerant (such as unconditioned attic spaces or boiler rooms), however, the
sections of the liquid line that are exposed to the warmer temperatures should
be insulated to prevent loss of subcooling.
liquid line
Other Considerations
▲ Pitch horizontal sections to run alongside
suction or discharge line
▲ Insulate lines that are routed through very
warm spaces
period five
Hot-Gas Bypass Line
The last refrigerant line to be considered is the hot-gas bypass line. The hot-gas
bypass line diverts hot, high-pressure refrigerant vapor from the discharge line
to the low-pressure side of the refrigeration system. This adds a “false load” to
the system that can help stabilize the suction pressure and temperature.
Hot-gas bypass is sometimes used to help prevent evaporator frosting in directexpansion (DX) applications, or in applications where the compressor cannot
be allowed to cycle on and off, such as a process-cooling application.
In general, however, hot-gas bypass should be avoided for most comfortcooling applications. It increases the refrigerant charge in the system, adds
more paths for potential refrigerant leaks, and increases the likelihood of
refrigerant-distribution and oil-return problems. It also increases the first cost of
the system, and the operating cost, because it prevents compressors from
cycling off with fluctuating loads.
period five
Hot-Gas Bypass Line
Refrigerant Piping
period five
Hot-Gas Bypass Line
Similar to the discharge line, the refrigerant flowing through the hot-gas bypass
line is in the form of a hot, high-pressure vapor. However, unlike the discharge
line, the minimum velocity is difficult to determine. A typical hot-gas bypass
valve is a modulating valve, so the refrigerant velocity through the valve and
piping can range all the way from zero flow to full flow. At times, the refrigerant
velocity inside a given pipe diameter will fall below the minimum velocity
required to carry oil droplets.
Therefore, it is not possible to select a pipe diameter that is small enough to
move oil at all valve positions. The hot-gas bypass line should be sized as small
as possible, without the maximum velocity being high enough to cause
objectionable noise. Because the hot-gas bypass line is basically an extension
of the discharge line, the recommended maximum velocity is 3,500 fpm
(17.5 m/s). Selecting the smallest possible line size also minimizes the amount
of oil and condensed refrigerant that could be trapped in the hot-gas bypass
line.
Also, the hot-gas bypass line must be installed so that oil and condensed
refrigerant can freely drain out of all sections of the line, at all operating
conditions.
hot-gas bypass line
Requirements for Sizing and Routing
▲ Ensure that oil and refrigerant are not trapped
in piping
▲ Avoid excessive noise
▲ Proper routing is more critical than pipe
diameter
period five
Hot-Gas Bypass Line
Hot-Gas Bypass to Evaporator Inlet
In a DX application, there are two bypass methods that are commonly used.
The first, and preferred, method bypasses refrigerant vapor from the
compressor discharge line to the inlet of the evaporator. Sensing a decrease in
suction pressure, the hot-gas bypass valve opens to bypass hot refrigerant
vapor from the compressor discharge line to the inlet of the evaporator,
between the TXV and the distributor. This adds a “false load” to the evaporator
and increases the suction pressure (and temperature).
The principal advantage of hot-gas bypass to the evaporator inlet is that the
refrigerant velocity inside the evaporator and the suction line is higher at low
loads. This promotes a uniform movement of oil through the evaporator and
the suction line.
Due to the widely varying velocity in the hot-gas bypass line, the selected
diameter of the pipe is not as critical as its routing. Install the hot-gas bypass
Hot-Gas Bypass to Evaporator Inlet
evaporator
condenser
compressor
hot-gas
bypass valve
TXV
distributor
suction line
liquid line
Figure 77
Hot-Gas Bypass Valve Installation
condenser
compressor
hot-gas
bypass valve
pitch back toward
discharge line
pilot
line
suction
line
discharge
line
pitch away
from hot-gas
bypass valve
hot-gas
bypass line
period five
Hot-Gas Bypass Line
valve above the discharge line and close to the compressor. Pitch the section of
pipe between the discharge line and the hot-gas bypass valve so oil will drain
back into the discharge line.
When using a pressure-actuated hot-gas bypass valve, tap the pilot line for the
valve close to the compressor inlet. This pilot line senses suction pressure, to
which the valve responds by modulating open or closed. Pitch the piping
downstream of the hot-gas bypass valve so that oil or condensed refrigerant
will drain away from the valve, toward the evaporator.
If the hot-gas bypass line includes a vertical riser of any height, or if the line
does not allow free drainage from the valve to the evaporator, the retention of
oil or condensed refrigerant within the riser must be considered. As mentioned,
because the refrigerant velocity within the hot-gas bypass line varies over a
wide range, no pipe, regardless of its diameter, can ensure adequate velocity to
carry oil up a riser of any height. Oil will collect at the base of the riser when the
hot-gas bypass valve throttles to lower flow rates.
This problem is commonly addressed by installing a small oil-return line
between the base of the riser and the suction line. First, a drain leg is provided
at the base of the riser to collect the oil and condensed refrigerant. This short
section of pipe should be about 12 in (300 mm) long and be the same diameter
as the riser.
Next, the oil-return line is connected to the side of the drain leg to prevent any
foreign material from plugging the tube. This oil-return line is constructed of
1/8 in. (3 mm)-diameter copper tubing and should be at least 5 ft (1.5 m) in
length. This length is required to create the necessary pressure drop between
the high-pressure and low-pressure sides of the system, yet this tubing is large
enough to drain oil and liquid refrigerant from the drain leg. If the oil-return line
must be longer than 5 ft (1.5 m), 1/4 in. (6 mm)-diameter tubing can be used for
the rest of the distance.
Hot-Gas Bypass Risers
hot-gas
bypass riser
suction
line
compressor
drain leg
oil-return
line
condenser
hot-gas
bypass valve
period five
Hot-Gas Bypass Line
The hot-gas bypass line is then piped to the evaporator inlet. It must be
connected to the top of the pipe, between the TXV and the distributor. Any hotgas bypass piping upstream of this connection should be pitched so that oil or
condensed refrigerant will drain toward the evaporator.
An orifice-type distributor is typically not able to permit adequate flow of
refrigerant vapor through the orifice. If this type of distributor is used, the
orifice must be relocated upstream of the point at which the hot-gas bypass line
connects to the distributor.
When the evaporator contains multiple distributors on a single refrigeration
circuit, the hot-gas bypass line should be piped to each distributor that is
“active” when the hot-gas bypass valve opens. The evaporator shown in
Figure 80 contains two distributors on the refrigeration circuit, each equipped
with a solenoid valve. In this example, the top solenoid valve closes when the
compressor unloads. Only the bottom distributor is “active” at minimum
capacity when the hot-gas bypass valve opens. Therefore, the hot-gas bypass
pipe only connects to the bottom distributor.
hot-gas bypass line
Connection to Evaporator
evaporator
distributor
liquid
line
hot-gas
bypass line
solenoid
valve
TXV
period five
Hot-Gas Bypass Line
The evaporator shown in Figure 81 also contains two distributors on a single
refrigeration circuit, but it only contains one solenoid valve. In this example, the
solenoid valve closes only after the last compressor on the circuit shuts off.
Both distributors are “active” at all times and the hot-gas bypass pipe must be
connected to both distributors.
When the hot-gas bypass line is piped to more than one distributor, check
valves should be installed in each section of pipe that feeds a distributor.
Without these check valves, a path is created between coil circuits whenever
the hot-gas bypass valve is closed. The coil circuits will become unequally
loaded and refrigerant will travel from the outlet of one TXV into the section of
coil that is served by a different TXV. This will result in the loss of superheat
control and potential compressor damage.
hot-gas bypass line
Connection to Evaporator
evaporator
distributor
hot-gas
bypass line
solenoid
valve
check
valves
TXV
period five
Hot-Gas Bypass Line
Hot-Gas Bypass to the Suction Line
The second bypass method conducts refrigerant vapor from the compressor
discharge line to the suction line. This method requires an additional expansion
valve, called a liquid-injection valve. The remote bulb of this liquid-injection
valve is attached to the suction line near the inlet to the compressor. When
reduced suction pressure causes the hot-gas bypass valve to open, the liquidinjection valve senses the resulting rise in suction temperature and opens to
mix liquid refrigerant with the bypassed refrigerant vapor. The hot refrigerant
vapor causes the liquid refrigerant to vaporize, cooling the mixture and
stabilizing the suction pressure.
The advantage of this method is that it requires less actual piping than
bypassing hot gas to the evaporator inlet. However, the disadvantage is that the
refrigerant velocity inside the evaporator and suction line (upstream of the hotgas bypass connection) can drop very low when the hot-gas bypass valve is
open. This may result in oil being trapped in the evaporator and the suction
line. For this reason, this method is only acceptable in applications where the
evaporator and the suction line are able to freely drain to the point at which the
hot-gas bypass line connects into the suction line. Therefore, hot-gas bypass to
the evaporator inlet is the preferred method.
Hot-Gas Bypass to Suction Line
evaporator
condenser
compressor
hot-gas
bypass valve
suction line
liquid line
liquid-injection
valve
TXV
period five
Hot-Gas Bypass Line
Again, routing of the hot-gas bypass piping is critical. Install the hot-gas bypass
valve above the compressor discharge and close to the compressor. Pitch the
section of pipe between the discharge line and the hot-gas bypass valve so that
oil will drain back into the discharge line. Tap the pilot line for the hot-gas
bypass valve close to the compressor inlet, and pitch the piping downstream of
the hot-gas bypass valve so that oil will drain away from the valve, toward the
suction line.
A separate pipe routes liquid refrigerant from the liquid line to mix with the hot,
bypassed refrigerant vapor. This mixture is then piped into the suction line at
an angle, at least 5 ft (1.5 m) upstream of the compressor inlet, and upstream of
the pilot line tap for the hot-gas bypass valve. This angled connection promotes
mixing, and the minimum distance helps ensure complete vaporization of the
liquid refrigerant before it reaches the compressor.
The liquid-injection line contains a thermal expansion valve, called a liquidinjection valve. The remote bulb for the liquid-injection valve is attached to the
suction line, downstream of the point at which the hot gas enters the suction
line. This valve is adjusted to maintain between 30°F and 35°F (-1°C and 1.5°C)
of superheat at the inlet to the compressor. A solenoid valve is installed
upstream of the liquid-injection valve to shut off the flow of liquid refrigerant
whenever the hot-gas bypass valve is closed.
hot-gas bypass line
Connection to Suction Line
condenser
compressor suction line
liquid
line
hot-gas
bypass valve
liquid-injection
valve
solenoid
valve
period five
Hot-Gas Bypass Line
Other Considerations
The hot-gas bypass valve, and the diameter of the hot-gas bypass line, are
selected based on the maximum amount of refrigerant vapor that will be
bypassed. This depends on the application and the purpose of the hot-gas
bypass system.
For a traditional comfort-cooling application, the hot-gas bypass valve is used
to modulate the amount of refrigerant vapor bypassed to maintain the suction
temperature at a setpoint, such as 28°F (-2.2°C). This typically requires the valve
to only open when the cooling load on the system drops below the minimum
compressor capacity.
For example, consider the same 20-ton (70.3-kW), single-circuit system that can
unload to a minimum capacity of 10 tons (35.2 kW). The hot-gas bypass valve
and line would probably be sized for 10 tons (35.2 kW) of capacity or less.
Assuming a maximum bypass capacity of 10 tons (35.2 kW), the refrigerant
velocity is determined for various pipe diameters using the chart in Figure 43
on page 34.
As explained at the beginning of this period, the diameter of the hot-gas bypass
line should be as small as possible while preventing the maximum velocity
from exceeding the recommended upper limit of 3,500 fpm (17.5 m/s). For this
example system, a 3/4 in. (18 mm)-diameter pipe is selected. If the overall
length of the hot-gas bypass line exceeds 75 ft (23 m), special precautions,
including increasing the line size, may be required.

period five
Hot-Gas Bypass Line
The full length of the hot-gas bypass line must be insulated to prevent the hot
refrigerant vapor from condensing before it reaches the evaporator.
As the length of the hot-gas bypass line increases, the risk of refrigerant vapor
condensing inside the line increases, even if the line is insulated. This can cause
a problem when the hot-gas bypass valve opens, because the refrigerant vapor
could force a slug of liquid refrigerant into the evaporator. This over-feeding of
the evaporator may cause liquid refrigerant to enter the suction line, possibly
slugging the compressor. For this reason, the overall length of the hot-gas
bypass line should be as short as possible.
If the refrigeration system includes a pump-down cycle, then a solenoid valve
must be installed in the hot-gas bypass line. A pump-down cycle closes the
liquid-line solenoid valve to stop the flow of refrigerant into the evaporator, and
allows the compressor to run for a short period of time. This pumps refrigerant
from the low-pressure side of the system (evaporator and suction line) to the
high-pressure side of the system (discharge line, condenser, and liquid line).
The solenoid valve in the hot-gas bypass line must also close when the system
begins the pump-down cycle, to prevent the high-pressure refrigerant vapor
from migrating to the low-pressure side of the system. Some hot-gas bypass
valves are equipped with an integral solenoid that can be used to hold the valve
closed for this purpose.
hot-gas bypass line
Other Considerations
▲ Insulate entire line to prevent refrigerant vapor
from condensing
▲ Minimize overall length of the line
▲ Install solenoid valve if system includes a
pump-down cycle
We will now review the main concepts that were covered in this clinic regarding
the design and installation of the interconnecting piping for vapor-compression
air-conditioning systems.
As discussed in Period One, when a refrigeration system includes fieldassembled refrigerant piping, the primary design goals are generally to
maximize system reliability and minimize installed cost. When the refrigerant
piping is designed and installed, it is imperative that the following requirements
are met:
 Return oil to the compressor at all operating conditions
 Ensure that only liquid refrigerant (no vapor) enters the expansion device
 Minimize system capacity loss that is caused by pressure drop through the
piping
period six
Review
Refrigerant Piping
Figure 86
Review—Period One
▲ Refrigerant Piping Requirements
◆ Return oil to compressor
◆ Ensure that only liquid refrigerant (no vapor) enters
the expansion device
◆ Minimize system capacity loss
◆ Minimize refrigerant charge
▲ If provided, use line sizes recommended
by the manufacturer
period six
Review
period six
Review  Minimize the total refrigerant charge in the system to improve reliability and
minimize installed cost
If the manufacturer of the refrigeration equipment provides recommended line
sizes, or tools for selecting the proper line sizes, use those line sizes.
Period Two reviewed the design of the suction line. The diameter of the suction
line should be selected small enough so the refrigerant velocity is high enough
to move oil, at all steps of compressor unloading. However, the pipe diameter
should be as large as possible to minimize pressure drop, maximize system
capacity and efficiency, and avoid causing objectionable noise.
The minimum allowable velocity in a suction line varies based on the diameter
of the pipe. The smaller the pipe diameter, the less velocity is required to move
the oil. Long line lengths and the associated higher pressure drop can be
tolerated, assuming that the loss of system capacity and efficiency is acceptable
for the given application. Of course, it is still good practice to minimize pressure
drop.
Review—Period Two
▲ Suction line
◆ Ensure adequate velocity to return oil to the
compressor at all steps of unloading
◆ Avoid excessive noise
◆ Minimize system capacity and efficiency loss
72 TRG-TRC006-EN
period six
Review
Period Three discussed the discharge line. Similar to the suction line, the
diameter of the discharge line must be small enough that the refrigerant
velocity is high enough to move oil, at all steps of compressor unloading.
However, the pipe diameter should be as large as possible to minimize
pressure drop, maximize system efficiency, and avoid causing objectionable
noise.
The liquid line was the focus of Period Four. The liquid line must be designed
and installed to ensure that only liquid refrigerant (no vapor) enters the
expansion device. This requires the condenser to provide adequate subcooling,
and the pressure drop through the liquid line and accessories must not be high
enough to cause flashing upstream of the expansion device.
An understanding of the entire refrigeration system, not just the piping, is
required to select the optimal liquid line size. The diameter of the liquid line
must be as small as possible to minimize the quantity of refrigerant in the
Review—Period Three
▲ Discharge line
◆ Ensure adequate velocity to return oil to the
compressor at all steps of unloading
◆ Avoid excessive noise
◆ Minimize efficiency loss
Review—Period Four
▲ Liquid line
◆ Ensure that only liquid refrigerant enters the
expansion device
◆ Minimize refrigerant charge
◆ Avoid excessive noise and pipe erosion
period six
Review
system and minimize the impact of changes in refrigerant density on the ability
of the condenser to provide subcooling. This improves system reliability and
minimizes the installed cost. However, if the pipe is too small, the increased
pressure drop may cause flashing upstream of the expansion device, and the
high velocity may result in objectionable noise or erosion to the inside surfaces
of the piping.
Period Five discussed the importance of proper routing when hot-gas bypass is
to be used. The two most common methods are hot-gas bypass to the
evaporator inlet and hot-gas bypass to the suction line. Hot-gas bypass to the
evaporator inlet is preferred because the refrigerant velocity in the evaporator
and the suction line is higher at low loads, resulting in improved oil return.
Because the hot-gas bypass valve modulates from full flow down to zero flow,
at times the refrigerant velocity will fall below the minimum velocity required to
carry oil droplets. Therefore, it is not possible to select a pipe diameter that is
small enough to move oil at all valve positions. The hot-gas bypass line must
be designed and installed so that oil and condensed refrigerant can freely drain
out of all sections of the line, at all operating conditions.
When used, the overall length of the hot-gas bypass line should be as short as
possible. In general, however, hot-gas bypass should be avoided for most
comfort-cooling applications.
Review—Period Five
▲ Hot-gas bypass line
◆ Ensure that oil and refrigerant are not trapped in the
piping
◆ Avoid excessive noise
◆ Proper routing is more critical than pipe diameter
period six


From*book-Trane Refrigerant Piping

ليست هناك تعليقات:

DWF

لتصاميم MEP  وتصميم انظمة التكييف المختلفه بالتعاون مع شركة  DWF  للتصاميم الهندسية  متخصصون فى مجال تهوية وتكييف المنازل ...

يتم التشغيل بواسطة Blogger.